SelECTING a Nitrogen Generator

To ensure the nitrogen generator is adequately sized, the following information is required:

STEP 1: SELECT A NITROGEN GENERATOR

To ensure the nitrogen generator is adequately sized, the following information is required:

1) The total cumulative size of all dry/preaction sprinkler systems

2) The size of the largest single dry/preaction sprinkler system

3) The total number of dry/preaction sprinkler systems

With this information an ECS nitrogen generator can be selected. Small to medium projects can generally be supplied with a pre-engineered nitrogen generator that includes an integral air compressor (PGEN-5/10/20). Projects with a larger cumulative sprinkler system capacity should be supplied with an engineered stand-alone nitrogen generator paired with a separate air compressor (PGEN-30/40/50/60).

STEP 2: SELECT A VENT

To facilitate the removal of oxygen, ECS utilizes the patented “fill and purge” breathing process which requires installation of a vent to control gas discharge from the fire sprinkler system. One (1) vent is required on each dry/preaction fire sprinkler riser, with two available options:

1) ECS Protector Manual Vent (PAV-D)

2) ECS Protector Dry SMART Vent (PSV-D)

The PAV-D is a mechanical device that is closed manually once the system nitrogen concentration has been verified at 98% or greater and represents the most economical approach to oxygen removal. The PSV-D includes an electronic sole- noid valve that closes automatically once the desired nitrogen concentration has been reached and is preferred in applica- tions that value automation or minimal human intervention.

STEP 3: SELECT MONITORING EQUIPMENT

Engineered Corrosion Solutions believes that a true corrosion management system should be monitored for performance to ensure that fire sprinkler system piping is properly protected against oxygen corrosion. ECS offers multiple monitoring options to pair with a nitrogen generation system:

STEP 4: CONTACT ORR PROTECTION SYSTEMS

ECS Selecting

NOTES:

  1. Single system capacity based on 30 min. fill requirement of largest single sprinkler system at 40 psi; a secondary air compressor with normally closed isolation valve can be used to meet fill requirement for larger individual systems
  2. Size and weight of nitrogen generator only, does not include separate air compressor
  3. 120V power supply required for nitrogen generator, 208 or 460V/3 phase power supply required for compressor
  4. Power requirement for stand alone nitrogen generator only, does not include separate air compressor power requirements, options include: 200V/230V/460V 3 phase
  5. PGEN-30 designed to receive air from oil-less compressed air supply only
  6. Lead time refers to time from order receipt to shipment from ECS facility, does not include shipping time
  7. Per ECS terms and conditions